| DISTRICT | NAME OF THE SCHOOL | # NOT WORKING | WIPRO INTERNAL COMPLAINT # | WCCC CALL # | WIPRO REMARKS | FIRST ATTENDED DATE | SECOND ATTENDED DATE | STATUS | CLOSED DATE | | | | | | |
| | | PART A | PART B | DATE OF COMPLAINT | | | | | | | | | | | | |
| DHUBRI | KUKURMARA ME SCHOOL | 2 | SSA/JUL/09 | 00350 | 1-Jul-09 | | Uniline: No electicity at the school as attended on 10.07.09. Main line is disconnected. School authority has asked to visit only after summer vacation is over./ Same situation is there as confirmed on 06.08.09/Attended on 21.08.09. But couldn't rectify due to Earthing problem. Earthing status as checked: ELECTICAL CONDITION NEUTRAL TO PHASE 165V
FACE TO EARTHING 135V
NEUTRAL TO EARTH 42V | 10.07.09 | 06.08.09 | PENDING FOR CUSTOMER | 21.08.09 | | | | | | |
| DHUBRI | R.B.P. H.S.SCHOOL | 2 | SSA/JUL/09 | 00351 | 1-Jul-09 | | Numeric: 2nos. 12v 26ah battery required. Battery Terminals Broken | | | BROKEN CASE NOT UNDER AMC | | | | | | | |
| GOALPARA | RAKHALDUBI HIGH MADRASSA | 2 | | | 15-Jul-09 | 1100198125 & 1100198124 | Numeric: Batteries are not available with 1 ups. Another is working fine as attended on 09.08.09 | 09.08.09 | | MISSING CASE NOT UNDER AMC | | | | | | | |
| DIBRUGARH | SOLOGURI ME SCHOOL | 1 | SSA/JUL/09 | 204 | 25-Jul-09 | 1100198134 | 12v 26ah 2nos. Battery need to be replaced with another one. | 27.08.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED AND REPLACED | 12.09.09 | | | | | | |
| BONGAIGAON | CHALANTAPARA GOVT MVS | 1 | SSA/JUL/09 | 223 | 28-Jul-09 | | Uniline: 4nos. Battery need to be replaced. 12v 26ah as attended on 29.07.09 | 29.07.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| BONGAIGAON | MANIKPUR SR. BASIC H.S.SCHOOL | 1 | SSA/JUL/09 | 224 | 28-Jul-09 | | Uniline: 1no. Battery need to be replaced. 12v 26ah as attended on 29.07.09 - Engineer went to replace batteries on 12.09.09, however, Principal did not allow engineer to replace the batteries | 29.07.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED AND REPLACED | | | | | | | |
| KARBI ANGLONG | PAROKHOWA HIG H SCHOOL | 1 | SSA/AUG/09 | 38 | 3-Aug-09 | 1100199419 | Uniline: Batteries are not available with the UPS as attended on 11.08.09 | 11.08.09 | | MISSING CASE NOT UNDER AMC | | | | | | | |
| MORIGAON | KUJISATRA ME SCHOOL | 1 | SSA/AUG/09 | 49 | 4-Aug-09 | 1300032035 | Uniline: 12v 26ah 4nos. Battery need to be replaced as attended on 18.08.09 | 18.08.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| DHUBRI | BIDYAPARA GIRLS' ME MADRASSA | 1 | SSA/AUG/09 | 165 | 6-Aug-09 | 1300032055 | Uniline:Transformer need to be replaced as attended on 17.08.09. Spare yet to be get. Earting stauts:NEUTRAL TO FACE 212V NEUTRAL TO EARTH 0V FACE TO NEUTRAL 0V. Untill and unless the rectification of the Earthing vendor will not attend the call. | 17.08.09 | | PENDING FOR CUSTOMER | | | | | | | |
| NALBARI | RAMPUR JANATA COMPOSITE SCHOOL | 1 | SSA/AUG/09 | 73 | 6-Aug-09 | 1100200557 | Uniline:Switch replaced.Now ups is working fine. Batteries are weak.Need replacement.12v26ah4nos. | 12.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| NALBARI | BHOJKUCHI MV SCHOOL | 1 | SSA/AUG/09 | 77 | 6-Aug-09 | 1100200559 | DS: UPS is working fine. Batteries are weak which need to be replaced. 12v 26ah 4nos. | 05.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| NALBARI | BHOJKUCHI MV SCHOOL | 1 | SSA/AUG/09 | 78 | 6-Aug-09 | 1100200560 | Uniline:339 IC replaced and call closed. But batteries are weak. Need to be replaced. 12v 26ah 4nos. | 05.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| JORHAT | SELENGHAT HS SCHOOL | 1 | SSA/AUG/09 | 61 | 6-Aug-09 | 1100200563 | Numeric: Batteries are weak. Need to be replaced. 12v 26ah 2nos. Both the UPS Have been replaced although it does not come under AMC as a gesture of goodwill | 29.08.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED AND REPLACED | | | | | | | |
| SONITPUR | F.A. AHMED ME SCHOOL | 2 | SSA/AUG/09 | 118&119 | 10-Aug-09 | 1100201016 & 1100201017 | Numeric: Found 1600HR UPS. UPSs are working fine. PCB Card Found Damaged when reattended - replaced as a gesture of goodwill | 20.08.09 | | BURNT CASE NOT UNDER AMC SCOPE RECTFIED AS A GESTURE OF GOODWILL | | | | | | | |
| DARRANG | TANGLA HS SCHOOL | 1 | SSA/AUG/09 | 149 | 11-Aug-09 | 1100201415 | Uniline(KL-DS-G3028):12v 26ah 4nos. Battery need to be replaced | 19.08.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| DHUBRI | NABABHARAT PATHSALA MES | 1 | SSA/AUG/09 | 152 | 12-Aug-09 | 1100202610 | Uniline(KL-HCL-G3153): Setting reset ac mode. Now ups is working fine. Batteries are weak.Need replacement. 12v 26ah 4nos. | 15.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| DHUBRI | BIDYAPARA GIRLS' ME MADRASSA | 1 | SSA/AUG/09 | 166 | 14-Aug-09 | | Numeric: Found 2kva UPS as attended on 25.08.09. UPS Found Damaged due to poor earthing conditions. Replaced the UPS as a Gesture of Goodwill on 12.10.09. Will not be replaced in future | 25.08.09 | | BURNT CASE NOT UNDER AMC SCOPE RECTFIED AS A GESTURE OF GOODWILL | 12.10.09 | | | | | | |
| NAGAON | JAGIAL GIRLS MES | 1 | SSA/AUG/09 | 176 | 14-Aug-09 | 1300032633 | Uniline: UPS is working fine. Batteries are weak. Need to be replaced. 12v 26ah 4nos. (2nos. UPS) | 07.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| KOKRAJHAR | BHOTGAON ME SCHOOL | 1 | SSA/AUG/09 | 212 | 20-Aug-09 | 1100203455 | Uniline: 1 battery need to be replaced 12v 7ah | 21.08.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| DHUBRI | SHAHEBGANJ ME SCHOOL | 1 | SSA/AUG/09 | 233 | 24-Aug-09 | 1300032539 | Uniline:UPS is working.Batteries are weak. Need to be replaced.12v26ah 4nos. | 14.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| GOALPARA | LAKHIPUR HS SCHOOL | 1 | SSA/AUG/09 | 240 | 24-Aug-09 | 1300032544 | Uniline: Ups is working fine. Batteries are weak. Need to be replaced. 12v 26ah 4nos. | 08.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| LAKHIMPUR | SABOTI WELFARE ME SCHOOL | 1 | SSA/AUG/09 | 302 | 29-Aug-09 | 1300032751 | Numeric:Found 2000hr UPS. UPS Found Damaged | 03.09.09 | | DAMAGED CASE NOT UNDER AMC SCOPE RECTFIED AS A GESTURE OF GOODWILL | 23.10.09 | | | | | | |
| LAKHIMPUR | LAHOLIAL MVS | 1 | SSA/AUG/09 | 307 | 31-Aug-09 | 1100206268 | NUMERIC: Found 2000hr ups. Batteris are weak.Need replacement.12v 7ah 8nos. | 04.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED AND REPLACED | 14.10.09 | | | | | | |
| LAKHIMPUR | SRIMANTA SHANKARDEV MES | 1 | SSA/AUG/09 | 320 | 31-Aug-09 | 1100206272 | Batteries of one UPS are weak. Need to be replaced. 12v 26ah 4nos. | 03.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| DHUBRI | SALKOCHA HS SCHOOL | 1 | SSA/AUG/09 | 331 | 31-Aug-09 | 1100206275 | NUMERIC:Found 1600HR UPS. Parts found damaged. Will be reattended | 04.09.09 | | DAMAGED CASE NOT UNDER AMC SCOPE HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| NALBARI | MILAN ME NARAYANPUR SCHOOL | 1 | SSA/SEP/09 | 36 | 5-Sep-09 | 1300033081 | NUMERIC:Found 2kva ups Will need to be re-attended Parts found damaged. Will be reattended | 10.09.09 | | DAMAGED CASE NOT UNDER AMC SCOPE HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| SIBSAGAR | RAJMAO MES | 1 | SSA/SEP/09 | 91 | 9-Sep-09 | 1300033151 | Uniline:UPS is working.Batteries are weak. Need to be replaced.12v26ah 4nos. | 14.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| SONITPUR | GAMIRI MVS | 1 | SSA/SEP/09 | 105 | 10-Sep-09 | 1300033255 | UNILINE(KL-DS-G3610):PCB TRACKS & COMPONENTS ARE BURNT & CHARGER CARD ALSO BURNT. UPS is irrepairable | 20.10.09 | | BURNT CASE NOT UNDER AMC | | | | | | | |
| GOLAGHAT | PULIBOR ADARSHA VIDYAPITH | 1 | SSA/SEP/09 | 47 | 11-Sep-09 | 1300033281 | UNILINE(KL-DS-G3672):UPS is working fine. Batteries are weak. Need replacement.12v 26ah 4nos. | 18.09.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| SONITPUR | BALICHANG MES | 1 | SSA/SEP/09 | 76 | 11-Sep-09 | 1300033290 | UNILINE(KLHCLH3175): School has been closed since from last couple of weeks as an Army base camp has made in the school. As confirmed by the school authority school will be re-open only after 7 to 10 days from the current day.Hence call is updated as Pending for customer | 21.10.09 | | PENDING FOR CUSTOMER | | | | | | | |
| JORHAT | NAMDEURI HS SCHOOL | 1 | SSA/SEP/09 | 137 | 14-Sep-09 | 1300033336 | NUMERIC:Short time back up. Batteries are weak. Need to be replaced. Details: 12v 26ah 2nos. | 13.10.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| DHUBRI | I.N.ACADEMY HS SCHOOL | 1 | SSA/SEP/09 | 151 | 14-Sep-09 | 1300033338 | NUMERIC:Found 1600HR UPS Will be reattended | 21.09.09 | | CLOSED | 22.10.09 | | | | | | |
| DHUBRI | JOGIRMAHAL ME SCHOOL | 1 | SSA/SEP/09 | 152 | 14-Sep-09 | 1300033339 | NUMERIC: Found 1600hr UPS. Reattend and parts found damaged. Although not under AMC, replaced UPS as gesture of goodwill | 21.09.09 | | DAMAGED CASE NOT UNDER AMC SCOPE RECTFIED AS A GESTURE OF GOODWILL | 10.10.09 | | | | | | |
| N.C.HILLS | NAZAETH HIGH SCHOOL | 1 | SSA/SEP/09 | 172 | 15-Sep-09 | 1300033385 | NUMERIC: | | | UNATTENDED | | | | | | | |
| SIBSAGAR | LAKWA MV SCHOOL | 1 | SSA/SEP/09 | 181 | 16-Sep-09 | 1300033410 | UNILINE:339IC and 8 Nos. of MOSFET are replaced | 15.10.09 | | CLOSED | 15.10.09 | | | | | | |
| JORHAT | BORBHETA MES | 1 | SSA/SEP/09 | 136 | 16-Sep-09 | 1300033335 | NUMERIC:Loose connection rectified | 12.10.09 | | CLOSED | 12.10.09 | | | | | | |
| NALBARI | BELSOR BALAK MES | 1 | SSA/SEP/09 | 155 | 18-Sep-09 | 1300033290 | NUMERIC:Found 2kva ups (Orient ups). | 05.10.09 | | ATTENDED | | | | | | | |
| SIBSAGAR | KHANAMUKH MES | 1 | SSA/SEP/09 | 201 | 18-Sep-09 | 1300033458 | NUMERIC:No ups problem found. UPS are working fine. | 06.10.09 | | FALSE CALL | | | | | | | |
| MORIGAON | JN ME SCHOOL | 1 | SSA/SEP/09 | 211 | 19-Sep-09 | 1100211259 | UNILINE:4nos. 540 mosfet replaced,on/off switch replaced | 01.10.09 | | CLOSED | 01.10.09 | | | | | | |
| SIBSAGAR | NITAIPUKHURI MV SCHOOL | 1 | SSA/SEP/09 | 214 | 19-Sep-09 | 1100211260 | NUMERIC: 8nos. Of Mosfet are changed.Now ups is working fine. | 14.10.09 | | CLOSED | 14.10.09 | | | | | | |
| SIBSAGAR | PALENGI ME SCHOOL | 1 | SSA/SEP/09 | 215 | 19-Sep-09 | 1100211261 | NUMERIC:UPS not back up in battery mood due to batteries are weak. Need replacement. 12v 26ah 2nos. | 21.10.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| BARPETA | BHAWANIPUR GIRLS ME SCHOOL | 1 | SSA/SEP/09 | 224 | 19-Sep-09 | 1100211262 | UNILINE: REPLACED IC339,3524IC & ON/OFF SWITCH. NOW UPS IS WORKING FINE | 10.10.09 | | CLOSED | 10.10.09 | | | | | | |
| NAGAON | RUPAHI MV SCHOOL | 1 | SSA/SEP/09 | 208 | 19-Sep-09 | 1100211257 | UNILINE:Due to electricity not available call couldn't attend/ REPLACED 324IC 2PC,3524IC,3391IC,4N35IC,540MOSFET 4PC,7812IC & 17 0 17 TRANSFORMER | 30.09.09 | 10.10.09 | CLOSED | 10.10.09 | | | | | | |
| NAGAON | JURIA HS SCHOOL | 1 | SSA/SEP/09 | 209 | 19-Sep-09 | 1100211258 | NUMERIC:No ups problem found. Confirmed with the PT, Mr. Nirab | 29.09.09 | | FALSE CALL | | | | | | | |
| NALBARI | SURADI ME SCHOOL | 1 | SSA/SEP/09 | 159 | 18-Sep-09 | 1300033539 | UNILINE:324ic replaced and ups is working in mains. To work in back up mood one spare need to be replaced/ 3524 IC,339IC,2 NOs of DIODE are replaced & also dry soldering done. | 07.10.09 | 15.10.09 | CLOSED | | | | | | | |
| GOALPARA | GOALPARA MES | 1 | SSA/SEP/09 | 205 | 18-Sep-09 | 1300033545 | NUMERIC:T2 transformer replaced and call closed | 08.10.09 | | CLOSED | 08.10.09 | | | | | | |
| GOALPARA | GOALPARA VIDYAPITH HS SCHOOL | 1 | SSA/SEP/09 | 206 | 18-Sep-09 | 1300033546 | NUMERIC:Loose connection rectified | 08.10.09 | | CLOSED | 08.10.09 | | | | | | |
| JORHAT | BALYA BHAWAN | 1 | SSA/SEP/09 | 227 | 22-Sep-09 | 1300033547 | UNILINE:REPLACED 339IC,& SWICH UPS IS WORKING FINE | 13.10.09 | | CLOSED | 13.10.09 | | | | | | |
| KARBI ANGLONG | OK-KERENG HIGH SCHOOL | 1 | SSA/SEP/09 | 230 | 22-Sep-09 | 1300033549 | UNILINE:Loose connection rectified and switch replaced | 20.10.09 | | CLOSED | 20.10.09 | | | | | | |
| KARBI ANGLONG | HOWRAGHAT GOVT MES | 1 | SSA/SEP/09 | 239 | 22-Sep-09 | 1300033552 | UNILINE:REPLACED T2 TRANSFORMER , NOW UPS IS WORKING IN BOTH MOOD | 20.10.09 | | CLOSED | 20.10.09 | | | | | | |
| SONITPUR | GANDHI MEMORIAL MES | 1 | SSA/SEP/09 | 250 | 24-Sep-09 | 1300033582 | UNILINE: 8 nos. of mosfet IRF 540n replaced and call closed | 05.10.09 | | CLOSED | 05.10.09 | | | | | | |
| BONGAIGAON | CHALANTAPARA GOVT MVS | 1 | SSA/SEP/09 | 252 | 24-Sep-09 | 1300033583 | UNILINE:Found UPS Circuit burnt.Not repairble at all. Earthing status also poor: Fuse to Neutrel 243v,Fuse to Ground 253v, Neutrel Ground 25v. | 16.10.09 | | BURNT CASE NOT UNDER AMC SCOPE | | | | | | | |
| DHEMAJI | JAMUGURI MV SCHOOL | 1 | SSA/SEP/09 | 268 | 29-Sep-09 | 1300033612 | UNILINE:339IC, 324IC & 4.5V ZINER DIOD REPLACED | 06.10.09 | | CLOSED | 06.10.09 | | | | | | |
| SIBSAGAR | LAKWA MV SCHOOL | 1 | SSA/SEP/09 | 272 | 29-Sep-09 | 1300033613 | UNILINE:324IC and 8 Nos. of MOSFET are replaced | 15.10.09 | | CLOSED | 15.10.09 | | | | | | |
| GOALPARA | FETENGAPARA ME SCHOOL | 1 | SSA/SEP/09 | 259 | 29-Sep-09 | 1300033610 | UNILINE:REPLACED 339 IC,7812 IC ,TESTED OK | 13.10.09 | | CLOSED | 13.10.09 | | | | | | |
| SIBSAGAR | RAJAPUKHURI MVS | 1 | SSA/SEP/09 | 276 | 30-Sep-09 | 1300033636 | NUMERIC:REPLACED 470MFD400V CAPACITOR,NOW UPS IS WORKING | 21.10.09 | | CLOSED | 21.10.09 | | | | | | |
| SONITPUR | BALIPARA MV SCHOOL | 1 | SSA/SEP/09 | 277 | 30-Sep-09 | 1300033637 | UNILINE:Capacitor burnt/ UPS taken on 21.10.09. Replacement provided and call closed | 05.10.09 | 21.10.09 | CLOSED | 23.10.09 | | | | | | |
| DHUBRI | BIDYAPARA GIRLS' ME MADRASSA | 1 | SSA/SEP/09 | 279 | 30-Sep-09 | 130033638 | UNILINE:Transformer need to be replaced as attended on 17.08.09. Spare yet to be get. Earting stauts:NEUTRAL TO FACE 212V NEUTRAL TO EARTH 0V FACE TO NEUTRAL 0V. Untill and unless the rectification of the Earthing vendor will not attend the call./DUPLICATE CALL LOGGED. Already have in pending sheet | 01.10.09 | | PENDING FOR CUSTOMER | | | | | | | |
| GOALPARA | DARRANGIRI MES | 1 | SSA/SEP/09 | 284 | 30-Sep-09 | 1300033642 | UNILINE:Dry soldiering done and call closed | 08.10.09 | | CLOSED | 08.10.09 | | | | | | |
| LAKHIMPUR | GOREHOGA GIRLS MES | 1 | SSA/SEP/09 | 286 | 30-Sep-09 | 1300033643 | NUMERIC:2000hr ups. | | | ATTENDED | | | | | | | |
| LAKHIMPUR | GOREHOGA GIRLS MES | 1 | SSA/SEP/09 | 287 | 30-Sep-09 | 1300033644 | NUMERIC:2000hr ups. | | | ATTENDED | | | | | | | |
| DIBRUGARH | BORPATHAR GIRLS ME | 1 | SSA/OCT/09 | 2 | 1-Oct-09 | 1300033671 | NUMERIC:As confirmed by the PT, Biswajit whole UPS had been replaced by SSA and need to be installed the same. So it's an installation case and doesn't cover the amc | 14.10.09 | | NEW REPLACEMENT FROM SSA NOT UNDER AMC | | | | | | | |
| JORHAT | CHENIAMGURI MES | 1 | SSA/OCT/09 | 4 | 5-Oct-09 | 1300033745 | UNILINE:REPLACED 339 IC ,324 IC, 3254IC, 12V RELAY | 12.10.09 | | CLOSED | 12.10.09 | | | | | | |
| MORIGAON | KAPAHERA GIRLS MES | 1 | SSA/OCT/09 | 7 | 5-Oct-09 | 1300033746 | NUMERIC:T2 transformer replaced and call closed | 21.10.09 | | CLOSED | 21.10.09 | | | | | | |
| BONGAIGAON | MALEGARH MES | 1 | SSA/OCT/09 | 20 | 5-Oct-09 | 1300033747 | UNILINE:SWITCH Replaced & loose connection rectified and ups is tested OK | 16.10.09 | | CLOSED | 16.10.09 | | | | | | |
| NAGAON | KACHUA MES | 1 | SSA/OCT/09 | 32 | 6-Oct-09 | 1300033754 | UNILINE:Dry soldiering done and call closed | 16.10.09 | | CLOSED | 16.10.09 | | | | | | |
| DHEMAJI | BATGHARIA MES | 1 | SSA/OCT/09 | 37 | 6-Oct-09 | 1300033756 | UNILINE:Planned on 27.10.09 | | | UNATTENDED | | | | | | | |
| DHEMAJI | BATGHARIA MES | 1 | SSA/OCT/09 | 38 | 6-Oct-09 | 1300033757 | UNILINE:Planned on 27.10.09 | | | UNATTENDED | | | | | | | |
| LAKHIMPUR | SRIMANTA SHANKARDEV MES | 1 | SSA/OCT/09 | 46 | 7-Oct-09 | 1300033804 | UNILINE:Planned on 26.10.09 | | | UNATTENDED | | | | | | | |
| TINSUKIA | MARGHERIA TOWN MES | 1 | SSA/OCT/09 | 48 | 8-Oct-09 | 1300033825 | UNILINE:REPLACED DC FUSE & LOOSE CONNECTION RECTIFIED | 22.10.09 | | CLOSED | 22.10.09 | | | | | | |
| MORIGAON | BHURBANDHA GIRLS ME SCHOOL | 1 | SSA/OCT/09 | 49 | 8-Oct-09 | 130033826 | UNILINE:Planned on 24.10.09 | | | UNATTENDED | | | | | | | |
| TINSUKIA | SARBAJANIN VALIKA VIDYALAY | 1 | SSA/OCT/09 | 50 | 8-Oct-09 | 1300033976 | UNILINE:CHANGED 339IC,SWITCH,UPS IS WORKING FINE | 23.10.09 | | CLOSED | 23.10.09 | | | | | | |
| KARBI ANGLONG | OK-KERENG HIGH SCHOOL | 1 | SSA/OCT/09 | 81 | 10-Oct-09 | 1300033549 | NUMERIC:Batteries are weak. 2nos. 12v 26ah need to be replaced | 20.10.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| TINSUKIA | SAIKHOWA ME SCHOOL | 2 | SSA/OCT/09 | 59 & 60 | 12-Oct-09 | 1300033865 & 1300033866 | UNILINE:REPLACED 3524IC UPS IS WORKING. Loose connection rectified of one UPS. | 23.10.09 | | CLOSED | 23.10.09 | | | | | | |
| BARPETA | TAPA ME SCHOOL | 1 | SSA/OCT/09 | 57 | 10-Oct-09 | 1300033864 | UNILINE:REPLACED 339IC, 4N45, ON/OFF SWITICH ,PCB WIRE CONNECTION DONE | 13.10.09 | | CLOSED | 13.10.09 | | | | | | |
| DHUBRI | F.A.MEMORIAL ME SCHOOL | 1 | SSA/OCT/09 | 61 | 10-Oct-09 | 1300033867 | UNILINE:Planned on 24.10.09 | | | UNATTENDED | | | | | | | |
| GOALPARA | DUDHNOI GIRLS ME SCHOOL | 1 | SSA/OCT/09 | 66 | 14-Oct-09 | 1300033998 | NUMERIC:Backup problem due to battery weak. 1no. 12v 26ah need to be replaced | 22.10.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| BONGAIGAON | RATNAPITH GIRLS MES | 1 | SSA/OCT/09 | 110 | 13-0CT-09 | 1300033953 | UNILINE:Planned on 23.10.09 | | | UNATTENDED | | | | | | | |
| SIBSAGAR | BIHUBAR MES | 1 | SSA/OCT/09 | 98 | 15-Oct-09 | 1300034024 | UNILINE:Replaced 339ic and transformer | 17.10.09 | | CLOSED | 17.10.09 | | | | | | |
| MORIGAON | TELAHI MV SCHOOL | 1 | SSA/OCT/09 | 115 | 15-0CT-09 | 1300034025 | UNILINE:Charging transformer is burnt. Ups not repairable | 20.10.09 | | BURNT CASE NOT UNDER AMC SCOPE | | | | | | | |
| SONITPUR | BALIPUKHURI MVS | 1 | SSA/OCT/09 | 126 | 16-0CT-09 | 1300034041 | UNILINE:REPLACED 339 IC, 3524IC, 324IC& BATTERY CABLE SOLDERING DONE, UPS IS WORKING IN BOTH MOOD | 19.10.09 | | CLOSED | 19.10.09 | | | | | | |
| DARRANG | JOYBHADARA HAGJER MES | 1 | SSA/OCT/09 | 134 | 19-Oct-09 | 1300034064 | NUMERIC:Planned on 24.10.09 | | | UNATTENDED | | | | | | | |
| KAMRUP | PANTAN ME SCHOOL | 1 | SSA/OCT/09 | 136 | 19-Oct-09 | 1300034065 | NUMERIC:8nos. 12 v 26ah Batteries are weak. Need to be replaced | 20.10.09 | | BATTERY REQUIRED DOES NOT COME UNDER AMC BEING CONSUMABLE, HOWEVER ORDER HAS BEEN PROCESSED | | | | | | | |
| TINSUKIA | TINGRAI ME SCHOOL | 1 | SSA/OCT/09 | 149 | 21-Oct-09 | 1300034165 | NUMERIC: | | | UNATTENDED | | | | | | | |
| CACHAR | DIGORKHAL HIGH SCHOOL | 1 | SSA/OCT/09 | 152 | 21-Oct-09 | 1300034166 | NUMERIC: | | | UNATTENDED | | | | | | | |
| DIBRUGARH | BOKPARA MES | 1 | SSA/OCT/09 | 157 | 21-Oct-09 | 1300034167 | NUMERIC: | | | UNATTENDED | | | | | | | |
| SONITPUR | BHOJKHOWA SIRAJIA MES | 1 | SSA/OCT/09 | 159 | 21-Oct-09 | 1300033290 | UNILINE: | | | UNATTENDED | | | | | | | |
| HAILAKANDI | PANDIT NARAYAN NATH MVS | 1 | SSA/OCT/09 | 162 | 21-Oct-09 | 1300034168 | NUMERIC: | | | UNATTENDED | | | | | | | |
| DHUBRI | GAURIPUR GIRLS HIGH SCHOOL | 1 | SSA/OCT/09 | 165 | 21-Oct-09 | 1300034169 | UNILINE: | | | UNATTENDED | | | | | | | |
| CACHAR | HBDS RAJABAZAR MVS | 1 | SSA/OCT/09 | 167 | 21-Oct-09 | 1300034170 | NUMERIC: | | | UNATTENDED | | | | | | | |
| CACHAR | LALANG MANIPURI MES | 1 | SSA/OCT/09 | 168 | 21-Oct-09 | 1300034171 | NUMERIC: | | | UNATTENDED | | | | | | | |
| DHEMAJI | BETIONIPAM MES | 1 | SSA/OCT/09 | 169 | 22-Oct-09 | 1300034199 | UNILINE: | | | UNATTENDED | | | | | | | |
| MORIGAON | BARANGABARI MV SCHOOL | 1 | SSA/OCT/09 | 173 | 22-Oct-09 | 1300034200 | UNILINE: | | | UNATTENDED | | | | | | | |
| KAMRUP | TUPAMARI ME SCHOOL | 1 | SSA/OCT/09 | 180 | 23-10-09 | 1300034218 | NUMERIC: | | | UNATTENDED | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |